Return Vents vs Supply Vents: Which Should Be Larger?
The war with the size of return vents vs supply vents has been going on since the introduction of forced air systems. It’s not a war of right and wrong either.
It’s a war with getting installers to read the book. As a rule of thumb, the return ducts added together should be the same size as all the supply ducts added together. But a rule of thumb is just an initial guide, not anything to bet your comfort on.
The science of airflow has always been available to any installer of HVAC equipment and ductwork. They just don’t follow the instructions very well in some cases where airflow is a problem.
You have to consider the length of duct and the type of duct and more. HVAC engineers have developed manuals to cover all the ins and outs of how to size ductwork.
Installers and technicians should understand the principles contained in:
ACCA Manuals J, S, and D are referenced and required across America. This form provides a quick and easy review of the HVAC system design. This review gives an objective indication of whether the required processes were followed.
Air Conditioning Contractors of America
There is a little attitude out there where companies will say, “We don’t need no stupid manuals,” and they can get away with it because they have done the same type of work over and over again with success.
And then there are those companies that install it all wrong. How are you going to know? I wrote an extensive article about questions you should ask when buying new HVAC stuff. They are even good questions to be familiar with as a homeowner with existing equipment.
Their are a few homes out there that have a return duct and a supply duct in each room, which really makes for a nice installation. With a return and supply in each room it’s important for them to be of an equivalent size so that the room is not over or under pressured.
For homes that have one or two main return ducts located in a hall or a great room, those returns should be equal in size to all the supplies throughout the home.
Basically the size of your duct work is determined by the size of your furnace. You size your furnace to be large enough to heat your home, and that furnace pushes or delivers so much airflow to keep the furnace from overheating.
Go look at your furnace’s factory label and look for the part on that label that’s giving a number for “external static pressure” similar to what’s on the label below circled in red.

A good technician will carry a gauge in his service truck called a manometer. Manometers can measure the static pressure across your furnace. The correct static pressure is one of the most critical settings in a heating and/or cooling system.
Manometers are easy to use. If you’re inclined to DIY this type of discovery, then click the button below to Amazon and see for yourself. Here’s a complete manometer kit that includes all the accessories that other manometers don’t include. Saves shopping around.
The wrong static pressure add huge issues in regards to efficiencies, service problems, and even make you think you bought a lemon.
What Happens If My Return Duct Is Too Small?
Several things are effected by duct work that is too small. One of the most noticeable characteristics of small ducts is noise. Your furnace has this static pressure designed to deliver quiet and efficient heating and cooling. Just the right amount nice quiet air in, out and through the system.
I like to relate this to an extreme. It make it easier for me anyway to understand.

Think about your return duct being the size of a straw. Wow, what a noise that would make! And talk about force. Fortunately it’s sucking in or it would be like an air nozzle off of an air compressor. It would blow your hat right off.
My daughter and her husband bought a house in Klamath Falls. Someone replaced an old oil high pressure system with a new gas furnace. High pressure systems have smaller duct work. Each run in the house was a 4″ duct.
It was so noisy you couldn’t hear yourself talk and the furnace ran so hot it was tripping the limit. We increased the size of the ducts and the temperature of the furnace came down to within specs.
This is why professionals in the HVAC industry use static pressure gauges. It’s a simple process of inserting a probe into the supply duct and another into the return at the location of the furnace.
What If My Return Duct Is Too Big?
Bigger can be better, but there are repercussions to that also. There are always repercussions when you go outside the limits of good duct design.
A squirrel cage blower has the characteristic of drawing higher amps with the more air that it can grab. Limiting the return to just the right amount can lower the amp draw. Saving you electricity and repairs.
Unlike a squirrel cage blower, a bladed fans amp draw will raise or go higher if you block it’s air flow.
Knowing the proper amp draw can only be determined by starting the blower and using an amp meter to see if the motor is running to specifications.
Most furnace blowers have an open housing that allows air to flow through the motor as it chugs away at moving air through the home. Blower still need to run at amp draws lower than the specified running amp or they will burn up in time.
I have used 110 volt blower in my shop to move air or remove dust and they are just an open blower with no duct. The amps tend to run a little high because of no static pressure.
I found if you just add a small strip of metal at the outlet that the amps drop and the motor runs nice and cool.
Conclusion Of Return Vents Vs Supply Vents
If you want to get more technical you’ll have to do some research elsewhere. I began this blog with the understanding that I would write in a way that the average home owner could understand without a degree in HVAC.
I’ve been around long enough that I didn’t have to complete an apprenticeship. I was grandfathered in with all my licenses. The younger technicians that I come across are so much more educated that I ever was or am because they apprenticed.
That is a blessing for homeowners, especially because of all the new technology available today. I hope your understanding of return vents vs supply vents is satisfactory.
Enjoyed the article. Well written. I replaced a 5 ton single speed Trane system with a 5 ton Ruud variable speed system for a 2,700 square foot cooling are in my home. The variable speed air handler was 24″ wide and they are proposing to replace it with a 21″ wide variable speed RUUD. Ruud has both a 21″ and a 24″ for 5 ton systems. I am concerned about sufficient air circulation and about the duct work being 24″ stepped down/up to 21″ air handler. Should I be? What are your thoughts.
Bob, equipment availability is a real problem these days. A five ton air handler should push five tons of air. I try to keep the same size unit as I’m replacing for ease of installation, but like I said they may be having an issue finding that same size and had to substitute. You could measure air flow before and after?